MAP 5300: Uninterruptible power supply repair verification Using the MAPs MAP 5400: Front panel

This MAP helps you to verify that FRUs that you have exchanged for new FRUs, or repair actions that have been done, have solved all the problems on the SAN Volume Controller uninterruptible power supply.

Prerequisites

If you are not familiar with these MAPs, read "Using the MAPs" first.

Context

You might have been sent here because you have performed a repair and want to confirm that no other problems exist on the machine.

Attention: Attention: If a SAN Volume Controller is powered off for more than five minutes and it is the only SAN Volume Controller connected to this uninterruptible power supply, the uninterruptible power supply will also power off. To power on the uninterruptible power supply, press and hold the On button until you hear the uninterruptible power supply beep (approximately one second) and the Mode indicator shows solid green.
Steps

Perform the following steps:

  1. Is the mode indicator for the repaired uninterruptible power supply illuminated solid green and the load level indicators showing an output load level between 25% and 100%?

    NO
    Continue with the start MAP.
    YES
    Go to step 2.
  2. (from step 1)

    Are all SAN Volume Controller nodes powered by repaired uninterruptible power supply Powered On?

    NO
    Press Power On on all SAN Volume Controller nodes that are powered off. Go to step 3.
    YES
    Go to step 3.
  3. (from step 2)

    Are any nodes still not Powered On or showing error codes in front panel display?

    NO
    Go to step 4.
    YES
    Continue with the start MAP.
  4. (from step 3)

    Do SAN Volume Controller nodes show Charging on front panel display?

    NO
    Go to step 5.
    YES
    Wait for Charging display to finish. (This might take up to 60 minutes). Go to step 5.
  5. (from step 4)

    Press and hold the Test/alarm reset button on the repaired uninterruptible power supply for three seconds to initiate a self-test. During the test individual indicators illuminate as various parts of the uninterruptible power supply are checked.

    Does the alarm beep or a uninterruptible power supply alarm indicator stay on?

    NO
    Uninterruptible power supply repair verification has been successfully completed. Continue with the repair verification MAP.
    YES
    Continue with the start MAP.
Related topics Using the MAPs MAP 5400: Front panel