This map helps you to solve problems that have occurred in the uninterruptible power systems used on a SAN Volume Controller.
If you are not familiar with these MAPs, read using the maps first.
You might have been sent here for one of the following reasons:
Figure 175 shows an illustration of the front of the panel for the uninterruptible power supply.
| 1 | Mode indicator | 2 | On button |
| 3 | Off button | 4 | Test/alarm reset button |
| 5 | Load level indicator | 6 | Site wiring fault indicator |
| 7 | Battery mode indicator | 8 | Battery power indicator |
| 9 | General alarm |

Perform the following steps:
Is the uninterruptible power supply connected to the failing SAN Volume Controller, Mode indicator off?
Are other uninterruptible power supplies showing Mode indicator off?
Is the uninterruptible power supply Mode indicator illuminated and flashing green?
Is the Mode indicator illuminated solid red?
Is the uninterruptible power supply Overload Load Level indicator illuminated red?
Is the uninterruptible power supply General Alarm indicator illuminated and flashing red? (This will cause a continuous audible alarm)
Is the uninterruptible power supply Battery Mode indicator illuminated and flashing red? (This causes an audible beep every five seconds).
Is the uninterruptible power supply Wiring Fault indicator illuminated and flashing red? (This causes an audible beep every five seconds).
Is the uninterruptible power supply Mode indicator flashing red? (This causes an audible beep every five seconds).
Are the uninterruptible power supply General Alarm, Battery Power, Battery Mode, Wiring Fault, Mode indicators illuminated and flashing red? (This causes a continuous audible alarm).