MAP 5200: Uninterruptible power supply Using the MAPs MAP 5300: Uninterruptible power supply repair verification

This map helps you to solve problems that have occurred in the uninterruptible power systems used on a SAN Volume Controller.

Prerequisites

If you are not familiar with these MAPs, read using the maps first.

Context

You might have been sent here for one of the following reasons:

Figure 175 shows an illustration of the front of the panel for the uninterruptible power supply.

 1  Mode indicator  2  On button
 3  Off button  4  Test/alarm reset button
 5  Load level indicator  6  Site wiring fault indicator
 7  Battery mode indicator  8  Battery power indicator
 9  General alarm    
Figure 175. Uninterruptible power supply front panel assembly
Uninterruptible power supply front panel assembly
Steps

Perform the following steps:

  1. Is the uninterruptible power supply connected to the failing SAN Volume Controller, Mode indicator off?

    NO
    Go to step 3.
    YES
    Go to step 2.
  2. (from step 1)

    Are other uninterruptible power supplies showing Mode indicator off?

    NO
    Power supply to this uninterruptible power supply is faulty or not connected correctly.
    1. Ask the customer to check the site power connection to this uninterruptible power supply.
    2. If input power connection is okay, replace the FRUs in the following sequence:
      1. Uninterruptible power supply power cord
      2. Uninterruptible power supply electronics assembly
      3. Uninterruptible power supply assembly
    3. Verify the repair by continuing with the uninterruptible power supply repair verification MAP.
    YES
    Main power is missing from installation
    1. Restore main power to installation
    2. Verify the repair by continuing with the uninterruptible power supply repair verification MAP.
  3. (from step 1)

    Is the uninterruptible power supply Mode indicator illuminated and flashing green?

    NO
    Go to step 4.
    YES
    The uninterruptible power supply is in standby mode. This may be because the SAN Volume Controllers powered by this uninterruptible power supply have been powered off for more than five minutes, or the Off button on this uninterruptible power supply has been pressed.
    1. Press and hold the On button until you hear the uninterruptible power supply beep (approximately one second) and the Power On indicator shows solid green. If the Mode indicator does not change to solid green replace the uninterruptible power supply electronics assembly.
    2. Verify the repair by continuing with the uninterruptible power supply repair verification MAP.
  4. (from step 3)

    Is the Mode indicator illuminated solid red?

    NO
    Go to step 8.
    YES
    The uninterruptible power supply is in bypass mode. Go to step 5
  5. (from step 4)

    Is the uninterruptible power supply Overload Load Level indicator illuminated red?

    NO
    Go to step 6.
    YES
    The uninterruptible power supply output power requirement exceeded the uninterruptible power supply capacity.
    1. Check that no more than four SAN Volume Controller nodes are connected to the uninterruptible power supply.
    2. Check that only SAN Volume Controller nodes are connected to the uninterruptible power supply.
    3. After ensuring output loading is correct, turn off and unplug the input power from the uninterruptible power supply. Wait at least 5 seconds until all LEDs are off and restart the uninterruptible power supply by reconnecting to input power and pressing the On button until you hear the uninterruptible power supply beep (approximately one second).
    4. If the condition persists, call the IBM support center.
    5. Verify the repair by continuing with the uninterruptible power supply repair verification MAP.
  6. (from step 5)

    Is the uninterruptible power supply General Alarm indicator illuminated and flashing red? (This will cause a continuous audible alarm)

    NO
    Go to step 7.
    YES
    The uninterruptible power supply internal temperature is too high.
    1. Turn off and unplug the uninterruptible power supply. Clear vents at the front and rear of the uninterruptible power supply. Remove any heat sources. Ensure the airflow around the uninterruptible power supply is not restricted.
    2. Wait at least 5 minutes and restart the uninterruptible power supply by reconnecting to input power and pressing the On button until you hear the uninterruptible power supply beep (approximately one second).
    3. If the condition persists, replace the uninterruptible power supply electronics assembly.
    4. Verify the repair by continuing with the uninterruptible power supply repair verification MAP.
  7. (from step 6)

    Is the uninterruptible power supply Battery Mode indicator illuminated and flashing red? (This causes an audible beep every five seconds).

    NO
    The uninterruptible power supply is in bypass mode because of an internal uninterruptible power supply fault.
    1. Replace in turn
      • Uninterruptible power supply electronics assembly
      • Uninterruptible power supply battery assembly
      • Uninterruptible power supply assembly
    2. Verify the repair by continuing with the uninterruptible power supply repair verification MAP.
    YES
    The uninterruptible power supply battery might be fully discharged or not connected correctly.
    1. Check that the uninterruptible power supply Battery assembly is installed correctly.
    2. Check that the uninterruptible power supply has been connected to a power outlet for at least 3 hours to charge the battery. After charging the battery, press and hold the Test/Alarm Reset Button for 3 seconds; then check the Battery Mode indicator.
    3. If the Battery Mode indicator is still on, replace the uninterruptible power supply Battery assembly.
    4. Verify the repair by continuing with the uninterruptible power supply repair verification MAP.
  8. (from step 4

    Is the uninterruptible power supply Wiring Fault indicator illuminated and flashing red? (This causes an audible beep every five seconds).

    NO
    Go to step 9.
    YES
    The uninterruptible power supply ground wire connection does not exist or the power input line and neutral wires are reversed.
    1. Check the grounding of the uninterruptible power supply.
    2. Ask the customer to check the uninterruptible power supply input power connection.
    3. Verify the repair by continuing with the uninterruptible power supply repair verification MAP.
  9. (from step 8)

    Is the uninterruptible power supply Mode indicator flashing red? (This causes an audible beep every five seconds).

    NO
    Go to step 10.
    YES
    The uninterruptible power supply is receiving input power that may be unstable or outside the specified voltage or frequency range. The SAN Volume Controller automatically adjusts the uninterruptible power supply voltage range. If the input voltage has recently changed, the alarm condition might be present until the SAN Volume Controller has adjusted the alarm setting. Ensure that an operational SAN Volume Controller is connected to the uninterruptible power supply. If the condition persists for at least five minutes, do the following:
    1. Ask the customer to check the site power for the uninterruptible power supply providing power to this SAN Volume Controller. Check the connection, voltage, and frequency.
    2. If input power is okay, replace the uninterruptible power supply electronics assembly.
    3. Verify the repair by continuing with the uninterruptible power supply repair verification MAP.
  10. (from step 9

    Are the uninterruptible power supply General Alarm, Battery Power, Battery Mode, Wiring Fault, Mode indicators illuminated and flashing red? (This causes a continuous audible alarm).

    NO
    The uninterruptible power supply is no longer showing a fault. Verify the repair by continuing with the uninterruptible power supply repair verification MAP.
    YES
    The uninterruptible power supply is reporting a fault condition.
    1. Replace in turn:
      • Uninterruptible power supply electronics assembly
      • Uninterruptible power supply battery assembly
      • Uninterruptible power supply assembly
    2. Verify the repair by continuing with the uninterruptible power supply repair verification MAP.
Related topics Using the MAPs MAP 5300: Uninterruptible power supply repair verification