Replacing the uninterruptible power supply
This task describes how to replace
the uninterruptible power supply after you have removed the previous uninterruptible
power supply.
 | Attention: Before you begin to install the uninterruptible power supply, read
the safety notices. |
 | CAUTION: The uninterruptible power supply contains its own energy source (batteries).
The output receptacles might carry live voltage even when the uninterruptible
power supply is not connected to an AC supply. (11) |
 | CAUTION: Do not remove or unplug the input cord when the uninterruptible power
supply is turned on. This removes the safety ground from the uninterruptible
power supply and the equipment connected to the uninterruptible power supply.
(12) |
 | CAUTION: To reduce the risk of fire or electric shock, install the uninterruptible
power supply in a temperature and humidity controlled, indoor environment,
free of conductive contaminants. Ambient temperature must not exceed 40°C
(104°F). Do not operate near water or excessive humidity (95%
maximum). (13) |
 | CAUTION: To avoid any hazard from the rack tipping forward when boxes are
installed, observe all safety precautions for the rack into which you are
installing the device. |
The uninterruptible power supply weighs 39 kg (86 lb)
with the electronics assembly and the battery assembly installed:
- Do not attempt to lift the uninterruptible power supply
by yourself. Ask another service representatives for assistance.
- Remove the battery assembly from the uninterruptible
power supply before removing the uninterruptible power supply from the shipping
carton.
- Do not attempt to install the uninterruptible power supply
into the rack unless the electronics assembly and the battery assembly have
been removed.
 | CAUTION: The electronics assembly weighs 6.4 kg (14 lb). Take care when you
remove it from the uninterruptible power supply. (16) |
 | CAUTION: The uninterruptible power supply battery unit weighs 21 kg (45 lb).
Do not attempt to lift the uninterruptible power supply battery unit by yourself.
Ask another service representative for aid. (18) |
Steps
Perform the following steps to replace the uninterruptible
power supply:
- The weight of the uninterruptible power supply must be reduced by removing
the battery assembly before removing it from the shipping carton. To remove
the battery assembly:
- Open the top of the uninterruptible power supply shipping carton and then
with the assistance of another service representative grip the flaps on either
side of the uninterruptible power supply. See Figure 156.
Figure 156. Two persons unboxing the uninterruptible power supply
- Slide the uninterruptible power supply to the end of the carton and rest
its front edge on the edge of the carton as shown. See Figure 157.
Figure 157. Slide the uninterruptible power supply to the edge of the carton
- Remove the two bolts 1 and additional nut 2 on
the left side of the bracket and remove the battery retaining bracket 3 . See Figure 158.
Figure 158. Remove the battery retaining bracket
- Grip the tab on the front of the battery and pull the battery forward
until it can be accessed by two service representatives.
- With the assistance of another service representative lift the battery
assembly clear of the uninterruptible power supply and place to one side.
 | Note: The cover for the uninterruptible power supply is not installed,
however, it is included in the box with the uninterruptible power supply.
Install the front cover after you have completed the other installation steps. |
-
With the assistance of another service representative, lift
the uninterruptible power supply onto a flat, stable surface.
- Remove the electronic assembly from the uninterruptible power supply:
- Remove the two screws 1 (see Figure 159).
Figure 159. Removing the uninterruptible power supply electronics assembly
- Pull the electronics assembly 2 out of the uninterruptible
power supply, and put it to one side.
- Stand at the front of the rack and, with aid from another service representative,
place the back of the uninterruptible power supply onto the support rails,
then slide the uninterruptible power supply into the rack.
- Install the front flathead screws 1 (see Figure 160).
Figure 160. Replacing the uninterruptible power supply into a rack
- With aid from another service representative, reinstall the following:
- Battery
- Electronics assembly
Attention: A grounding screw feature is provided
on the back of the uninterruptible power supply so that you can attach a ground
bonding wire if required by local wiring codes. Since safety earthing of the
uninterruptible power supply chassis is maintained through the input line
power cord, you are usually not required to use this additional grounding
screw feature.
- Reconnect the signal cables.
- Install the front panel.
- At the back of the uninterruptible power supply, plug the uninterruptible
power supply main power cable into the power socket, 1 in Figure 161.
 | Note: The uninterruptible power supply is intended
to maintain power on SAN Volume Controller nodes until data can be saved to the local hard
disk drive. Only SAN Volume Controller nodes can be plugged into the uninterruptible power
supply or the SAN Volume Controller cluster malfunctions. |
Figure 161. Installing the uninterruptible power supply power cable
 | Attention: If possible, ensure that the two uninterruptible power supplies
are not connected to the same power source. |
 | Note: The
uninterruptible power supply requires a dedicated branch circuit that meets
the following specifications:
- One 15A circuit breaker in each branch circuit supplies the power to a
uninterruptible power supply
- Single-phase
- 50 to 60 Hz
- 200 - 240 Volt
|
- All the front panel indicators (see Figure 162) flash for
a short time while the uninterruptible power supply runs a self test. When
the test is complete, the mode indicator, 1 in Figure 162,
flashes to show that the uninterruptible power supply is in standby mode.
Press and hold the uninterruptible power supply on the switch, 2 in Figure 162, until you hear the uninterruptible power supply beep (approximately
one second). The mode indicator stops flashing and the load level indicators
display the percentage of load that is being supplied by the uninterruptible
power supply. The uninterruptible power supply is now in normal mode, and
is charging its battery.
Figure 162. Power switch and indicators of the uninterruptible power supply
Related topics