Removing the system board
The following task describes how
to remove the system board.
The system board FRU is a kit that includes the following parts:
- PCI riser card
- Two microprocessors
- Microprocessor voltage regulator module (VRM)
- Planar
Use all the parts in the kit when you replace the system board FRU.
The system board is electrostatic-discharge (ESD) sensitive. Take precautions
to avoid damage from static electricity.
Steps
Perform the following steps to remove the system board:
- Remove all power from the SAN Volume Controller.
- Remove the SAN Volume Controller from the rack.
- Remove the top cover of the SAN Volume Controller 1 .
-
If you are going to exchange the system board for another
system board, go to step 5. Otherwise, go to step 7.
-
Remove the adapter assemblies. Keep the adapter assemblies;
they must be installed onto the replacement system board.
-
Remove the memory modules. Keep the memory modules; they
must be installed onto the replacement system board.
Figure 151. Removing the system board
-
Disconnect:
- All fan connectors
- Power connectors P1 and P2
- SCSI power connector
- ATA connector
- Disk drive connectors
- Service Controller connector
- Lift out the air baffle.
- Unscrew the heat sink captive screws 4 .
- Move the heat sinks gently from side to side to break the seal
formed by the thermal compound and then pull them off the processors.
- Remove the screws from each of the heat sink retainer brackets 3 .
- Remove the retainer brackets.
- Remove the two screws from each of the three connectors.
- Remove the seven screws 2 .
- Remove the system board.
- If you have any other tasks to do inside the SAN Volume Controller, do those tasks now.
Otherwise, reinstall parts in the reverse sequence.
 | Notes:
- Use all the parts in the system board FRU kit (system board, processors
(2), VRM, riser card). Re-use only the four memory modules that you removed
in step 6 and the two adapter assemblies that you removed
in step 4.
- Before you install the new system board, check whether the old system
board has any jumpers installed. If it has, install matching jumpers onto
the new system board.
- Before you install the processors on the system board, remove the dust
covers from the processor socket.
- If you were not sent here from the directed maintenance procedures rewrite
the SAN Volume Controller serial number. If you were sent here from directed maintenance procedures
this step will be performed from within the procedure.
- CAREFULLY install the end of the ribbon cable (marked "System Planar")
to the system board being sure to install the cable straight in. See Figure 152. Be sure to verify that the blue line on the cable
connector end is not visible.
|
Figure 152. Install service controller cable into the system board