MAP 5000: Start Using the MAPs MAP 5100: Power

This MAP is the entry point to the MAPs for the SAN Volume Controller.

Prerequisites

If you are not familiar with these MAPs, read "Using the MAPs" first.

Context

You might have been sent here for one of the following reasons:

SAN Volume Controllers are configured in pairs. While you service one SAN Volume Controller, the other permits access to all the storage managed by the pair. With concurrent maintenance, all FRUs can be removed, replaced, and tested on one SAN Volume Controller while the SAN and host systems are powered on and doing productive work

Note:Note: Unless you have a particular reason to do so, do not remove the power from both SAN Volume Controllers unless these instructions tell you to do so.
Steps

Perform the following steps:

  1. Were you sent here from a Directed Maintenance Procedure?
    NO
    Go to step 2
    YES
    Go to step 8
  2. (from step 1)

    Find the master console that is used to access the SAN Volume Controller cluster. This is normally located in the same rack as the SAN Volume Controllers but might be located in another rack if the master console is used to support more than one SAN Volume Controller cluster.

  3. (from step 2)

    Log on to the master console using the user ID and password provided by the customer.

  4. (from step 3)

    Log in to the SAN Volume Controller Console using the user ID and password provided by the customer, and launch the SAN Volume Controller application for the cluster you are repairing.

  5. (from step 4)

    Does the SAN Volume Controller application start?

    NO
    Go to step 8.
    YES
    Go to step 6.
  6. (from step 5)

    When the SAN Volume Controller cluster that you want to service is selected, is the Welcome panel displayed?

    NO
    Go to step 8.
    YES
    Go to step 7.
  7. (from steps 1, 5, and 6)

    Start the Directed Maintenance Procedures.

    Did the maintenance procedures find an error that needs to be fixed?

    NO
    Go to step 8.
    YES
    Follow the Directed Maintenance Procedures.
  8. (from steps 1, 5, 6, and 7)

    Is the power light on any SAN Volume Controller front panel off or flashing?

    NO
    Go to step 9.
    YES
    Go to power map.
  9. (from step 8)

    Is the front panel check light on any SAN Volume Controller illuminated?

    NO
    Go to step 10.
    YES
    The service controller for the SAN Volume Controller failed.
    1. Replace the service controller in the SAN Volume Controller with the check light on.
    2. Go to the Repair Verification MAP.
  10. (from step 9)
    Figure 174. Hardware boot display
    Hardware boot display

    Is the hardware boot display that you see in Figure 174 displayed on any of the SAN Volume Controllers?

    NO
    Go to step 12.
    YES
    Go to step 11.
  11. (from step 10)

    Has the hardware boot display that you see in Figure 174 displayed for more than three minutes?

    NO
    Go to step 12.
    YES
    1. Go to Determining a hardware boot failure.
    2. Go to the Repair Verification MAP.
  12. (from steps 10 and 11)

    Is Failed displayed on the top line of the service display of any SAN Volume Controller?

    NO
    Go to step 13.
    YES
    1. Note the failure code. Go to Understanding the Boot codes and perform the repair actions.
    2. Go to the Repair Verification MAP
  13. (from step 12)

    Is Booting displayed on the top line of the service display of any SAN Volume Controller?

    NO
    Go to step 15.
    YES
    Go to step 14.
  14. (from step 13)

    A progress bar and a boot code are displayed. If the progress bar does not advance for more than three minutes it has stalled.

    Has the progress bar stalled?

    NO
    Go to step 15.
    YES
    1. Note the failure code. Go to Understanding the Boot codes and perform the repair actions.
    2. Go to the Repair Verification MAP.
  15. (from steps 13 and 14)

    If any of the navigation buttons on the front panel have been pressed, you should now wait for sixty seconds to ensure that the display has switched to its default display.

    Is Node Error displayed on the top line of the service display of any SAN Volume Controller?

    NO
    Go to step 16.
    YES
    1. Note the failure code. Go to Understanding the node error codes and perform the repair actions.
    2. Go to the Repair Verification MAP.
  16. (from step 15)

    Is Cluster Error displayed on the top line of the service display of any SAN Volume Controller?

    NO
    Go to step 17.
    YES
    1. A cluster error has been detected. This error code will be displayed on all the operational nodes in the cluster. This type of error should normally be repaired using the Directed Maintenance Procedures. If you are unable to start the directed maintenance procedures then go to Cluster error codes and perform the repair actions.
    2. Go to the Repair Verification MAP.
  17. (from step 16)

    Is Powering Off, Restarting, Shutting Down, or Power Failure displayed in the top line of the service display?

    NO
    Go to step 19.
    YES
    The progress bar will move every few seconds. Wait for the operation to complete and then return to step 1 in this MAP. If the progress bar does not move for three minutes, press the power button and go to step 18.
  18. (from step 17)

    Did the SAN Volume Controller power off?

    NO
    1. Remove the power cord from the rear of the box.
    2. Wait 60 seconds.
    3. Replace the power cord.
    4. If the node does not power on, press the power button to power on the SAN Volume Controller, then return to step 1 in this MAP.
    YES
    1. Wait 60 seconds.
    2. Press the power button to power on the SAN Volume Controller, then return to step 1 in this MAP.
    Note:Note: If the SAN Volume Controller is powered off for more than five minutes and it is the only SAN Volume Controller connected to the uninterruptible power supply, the uninterruptible power supply will also power off. Before pressing the power button on the SAN Volume Controller you will need to press the power on button on the uninterruptible power supply.
  19. (from step 18)

    Is Charging or Recovering displayed in the top line of the service display of any SAN Volume Controller?

    NO
    Go to step 20.
    YES
    If Charging is displayed the uninterruptible power supply battery is not yet charged sufficiently to support the SAN Volume Controller. If this is displayed for more than three hours go to the Uninterruptible power supply MAP. If Recovering is displayed the uninterruptible power supply battery is not yet charged sufficiently to be able to support the SAN Volume Controller immediately following a power supply failure, however, while Recovering is displayed the SAN Volume Controller Controller can be used normally. If Recovering is displayed for more than two hours go to the Uninterruptible power supply MAP.
  20. (from step 19)

    Is the service display unreadable?

    NO
    Go to step 21.
    YES
    1. The display might be set to another language.
    2. If the language is set correctly, go to front panel map.
  21. (from step 20)

    No errors have been detected by the SAN Volume Controller. If you suspect that the problem reported by the customer is a hardware problem perform the following tasks:

    1. Perform problem determination procedures on your host systems, disk controllers, and fibre channel switches.
    2. Ask your hardware support center for assistance.

If you suspect that the problem is a software problem, go to Installing and maintaining the software for the SAN Volume Controller.