This MAP is the entry point to the MAPs for the SAN Volume Controller.
If you are not familiar with these MAPs, read "Using the MAPs" first.
You might have been sent here for one of the following reasons:
SAN Volume Controllers are configured in pairs. While you service one SAN Volume Controller, the other permits access to all the storage managed by the pair. With concurrent maintenance, all FRUs can be removed, replaced, and tested on one SAN Volume Controller while the SAN and host systems are powered on and doing productive work
| Note: Unless you have a particular reason to do so, do not remove the power from both SAN Volume Controllers unless these instructions tell you to do so. |
Perform the following steps:
Find the master console that is used to access the SAN Volume Controller cluster. This is normally located in the same rack as the SAN Volume Controllers but might be located in another rack if the master console is used to support more than one SAN Volume Controller cluster.
Log on to the master console using the user ID and password provided by the customer.
Log in to the SAN Volume Controller Console using the user ID and password provided by the customer, and launch the SAN Volume Controller application for the cluster you are repairing.
Does the SAN Volume Controller application start?
When the SAN Volume Controller cluster that you want to service is selected, is the Welcome panel displayed?
Start the Directed Maintenance Procedures.
Did the maintenance procedures find an error that needs to be fixed?
Is the power light on any SAN Volume Controller front panel off or flashing?
Is the front panel check light on any SAN Volume Controller illuminated?

Is the hardware boot display that you see in Figure 174 displayed on any of the SAN Volume Controllers?
Has the hardware boot display that you see in Figure 174 displayed for more than three minutes?
Is Failed displayed on the top line of the service display of any SAN Volume Controller?
Is Booting displayed on the top line of the service display of any SAN Volume Controller?
A progress bar and a boot code are displayed. If the progress bar does not advance for more than three minutes it has stalled.
Has the progress bar stalled?
If any of the navigation buttons on the front panel have been pressed, you should now wait for sixty seconds to ensure that the display has switched to its default display.
Is Node Error displayed on the top line of the service display of any SAN Volume Controller?
Is Cluster Error displayed on the top line of the service display of any SAN Volume Controller?
Is Powering Off, Restarting, Shutting Down, or Power Failure displayed in the top line of the service display?
Did the SAN Volume Controller power off?
| Note: If the SAN Volume Controller is powered off for more than five minutes and it is the only SAN Volume Controller connected to the uninterruptible power supply, the uninterruptible power supply will also power off. Before pressing the power button on the SAN Volume Controller you will need to press the power on button on the uninterruptible power supply. |
Is Charging or Recovering displayed in the top line of the service display of any SAN Volume Controller?
Is the service display unreadable?
No errors have been detected by the SAN Volume Controller. If you suspect that the problem reported by the customer is a hardware problem perform the following tasks:
If you suspect that the problem is a software problem, go to Installing and maintaining the software for the SAN Volume Controller.