Removing the uninterruptible power supply Removing parts Removing the support rails for an uninterruptible power supply

The following task describes how to remove the uninterruptible power supply.

Attention: Attention: Before you begin to remove the uninterruptible power supply, read the safety notices.
CAUTION:CAUTION: The uninterruptible power supply contains its own energy source (batteries). The output receptacles might carry live voltage even when the uninterruptible power supply is not connected to an AC supply. (11)
CAUTION:CAUTION: Do not remove or unplug the input cord when the uninterruptible power supply is turned on. This removes the safety ground from the uninterruptible power supply and the equipment connected to the uninterruptible power supply. (12)
CAUTION:CAUTION: To reduce the risk of fire or electric shock, install the uninterruptible power supply in a temperature and humidity controlled, indoor environment, free of conductive contaminants. Ambient temperature must not exceed 40°C (104°F). Do not operate near water or excessive humidity (95% maximum). (13)
CAUTION:CAUTION: To avoid any hazard from the rack tipping forward when boxes are installed, observe all safety precautions for the rack into which you are installing the device.
CAUTION:CAUTION: The electronics assembly weighs 6.4 kg (14 lb). Take care when you remove it from the uninterruptible power supply. (16)
CAUTION:CAUTION: The uninterruptible power supply battery unit weighs 21 kg (45 lb). Do not attempt to lift the uninterruptible power supply battery unit by yourself. Ask another service representative for aid. (18)
Context

Removing the uninterruptible power supply requires that you first remove the uninterruptible power supply electronics and the uninterruptible power supply battery.

Steps

Perform the following steps to remove the uninterruptible power supply.

CAUTION:CAUTION: Check to make sure that any SAN Volume Controller that is powered by this uninterruptible power supply are shut down and powered off, prior to step 1.
  1. At the front of the uninterruptible power supply, press and hold the off button  1  for approximately five seconds or until the long beep stops. See Figure 123.
    Figure 123. Uninterruptible power supply front panel assembly
    Uninterruptible power supply front panel assembly
  2. At the back of the uninterruptible power supply, disconnect the power cables of the SAN Volume Controller  3 .
  3. Disconnect the signal cables  1 .
  4. Disconnect the main power cable 2 . See Figure 124.
    Figure 124. Uninterruptible power supply (rear view)
    Uninterruptible power supply (rear view)
  5. Remove the battery from the uninterruptible power supply. Refer to the procedure for removing uninterruptible power supply battery.
    CAUTION:CAUTION: The uninterruptible power supply battery unit weighs 21 kg (45 lb). Do not attempt to lift the uninterruptible power supply battery unit by yourself. Ask another service representative for aid. (18)
    Note:Note: For the translation of the danger, caution, attention notices, and the translation of the safety labels, see IBM TotalStorage Open Software Family SAN Volume Controller Translated Safety Notices.
  6. Remove the electronics assembly from the uninterruptible power supply. Refer to the procedure for removing the uninterruptible power supply electronics assembly.
  7. At the front of the uninterruptible power supply, unscrew the mounting screws,  1  in Figure 125.

    Figure 125. Removing the uninterruptible power supply
    Removing the uninterruptible power supply
  8. At the back of the rack, push the uninterruptible power supply forward approximately 5 cm (2 in).

    Attention: Do not push the uninterruptible power supply too far forward.

  9. Go to the front of the rack.
  10. With aid from another service representative, pull the uninterruptible power supply forward and remove it from the rack.
  11. To replace the uninterruptible power supply refer to the procedure for replacing the uninterruptible power supply.