This topic provides information you need to ensure that your physical site meets the installation requirements for the uninterruptible power supply.
| Attention: Ensure that you comply with the following requirements for : |
| Note: If the uninterruptible power supply is cascaded from another uninterruptible power supply, the source uninterruptible power supply must have at least 3 times the capacity per phase and the total harmonic distortion must be less than 5% with any single harmonic being less than 1%. The uninterruptible power supply must also have input voltage capture that has a slew rate faster than 3 Hz per second and 1 msec glitch rejection. |
| Height | Width | Depth | Maximum weight |
|---|---|---|---|
| 89 mm
(3.5 in.) |
483 mm
(19 in.) |
622 mm
(24.5 in.) |
39 kg
(86 lb.) |
| Power supply assembly type | Voltage | Frequency |
|---|---|---|
| 220 V | 160 to 288 V ac | 46 to 64 Hz |
Operating environment |
Nonoperating environment |
Storing environment |
Shipping environment |
|
|---|---|---|---|---|
Air temperature |
0°C to 40°C (32°F to 104°F) |
0°C to 40°C (32°F to 104°F) |
0°C to 25°C (32°F to 77°F) |
-25°C to 55°C (-13°F to 131°F) |
Relative humidity |
5% to 95% noncondensing |
5% to 95% noncondensing |
5% to 95% noncondensing |
5% to 95% noncondensing |
Operating environment |
Nonoperating environment |
Storing environment |
Shipping environment |
|
|---|---|---|---|---|
Altitude (from sea level) |
0 to 2000 m (0 to 6560 ft.) |
0 to 2000 m (0 to 6560 ft.) |
0 to 2000 m (0 to 6560 ft.) |
0 to 15 000 m (0 to 49 212 ft.) |
142 watts (485 Btu per hour) during normal operation.
553 watts (1887 Btu per hour) when power has failed and the uninterruptible power supply is supplying power to the nodes of the SAN Volume Controller.