This topic provides information you need to ensure that your physical site meets the installation requirements for the SAN Volume Controller.
| Height | Width | Depth | Approximate Maximum Weight |
|---|---|---|---|
| 43 mm
(1.7 in.) |
440 mm
(17.3 in.) |
660 mm
(26 in.) |
12.7 kg
(28 lb.) |
| Location | Additional space required | Reason |
|---|---|---|
| Left- and right-hand sides | 50 mm (2 in.) | Cooling air flow |
| Back | 100 mm (4 in.) minimum | Cable exit |
| Power Supply Assembly Type | Voltage | Frequency |
|---|---|---|
| 220 V | 88 to 264 V ac |
47 to 63 Hz
|
| Environment | Temperature | Altitude | Relative humidity |
Maximum wet bulb temperature |
|---|---|---|---|---|
| Operating | 10°C to 35°C (50°F to 95°F) |
0 to 914 m (0 to 2998 ft.) |
8% to 80% noncondensing |
23°C (74°F ) |
10°C to 32°C (50°F to 88°F) |
914 to 2133 m (2998 to 6988 ft.) |
8% to 80% noncondensing |
23°C (74°F ) | |
| Powered off | 10°C to 43°C (50°F to 110°F) |
- | 8% to 80% noncondensing |
27°C (81°F ) |
| Storing | 1°C to 60°C (34°F to 140°F) |
0 to 2133 m (0 to 6988 ft.) |
5% to 80% noncondensing |
29°C (84°F) |
| Shipping | -20°C to 60°C (-4°F to 140°F) |
0 to 10668 m (0 to 34991 ft.) |
5% to 100% condensing, but no precipitation |
29°C (84°F) |