The uninterruptible power supply provides the SAN Volume Controller with a secondary power source to be used if you lose power from your primary power source due to power failures, power sags, power surges, or line noise. If a power outage occurs, the uninterruptible power supply will maintain power long enough to save any configuration and cache data contained in the dynamic random access memory (DRAM). The data will be saved to the SAN Volume Controller internal disk.

| Note: The SAN Volume Controller uninterruptible power supply is an integral part of the SAN Volume Controller solution, and maintains continuous SAN Volume Controller-specific communications with its attached SAN Volume Controller nodes. The SAN Volume Controller uninterruptible power supply must be used in accordance with documented guidelines and procedures and must not be used for any other purpose. |
To provide full redundancy and concurrent maintenance, SAN Volume Controllers must be installed in pairs. Each SAN Volume Controller of a pair must be connected to a different uninterruptible power supply. Each uninterruptible power supply can support up to two SAN Volume Controller nodes. It is also recommended that you connect the two uninterruptible power supply units for the pair to different independent electrical power sources. This reduces the chance of an input power failure at both uninterruptible power supply units.
Attention:
|
Each uninterruptible power supply includes power (line) cords that will connect the uninterruptible power supply to either a rack power distribution unit (PDU), if one exists, or to an external power source. Each uninterruptible power supply power input requires the protection of a UL approved (or equivalent) 250 volt, 15 amp circuit breaker.
The uninterruptible power supply is connected to the SAN Volume Controllers with a power cable and a signal cable. To avoid the possibility of power and signal cables being connected to different uninterruptible power supply units, these cables are wrapped together and supplied as a single field replaceable unit. The signal cables enable the SAN Volume Controllers to read status and identification information from the uninterruptible power supply.
Each SAN Volume Controller monitors the operational state of the uninterruptible power supply to which it is attached. If the uninterruptible power supply reports a loss of input power, the SAN Volume Controller stops all I/O operations and dumps the contents of its DRAM to the internal disk drive. When input power to the uninterruptible power supply is restored, the SAN Volume Controllers restart and restore the original contents of the DRAM from the data saved on the disk drive.
A SAN Volume Controller is not fully operational until the uninterruptible power supply battery charge state indicates that it has sufficient capacity to power the SAN Volume Controller for long enough to permit it to save all its memory to the disk drive in the event of a power loss. The uninterruptible power supply has sufficient capacity to save all the data on the SAN Volume Controller at least twice. For a fully-charged uninterruptible power supply, even after battery capacity has been used to power the SAN Volume Controllers while they save DRAM data, sufficient battery capacity will remain to let the SAN Volume Controllers become fully operational as soon as input power is restored.
| Note: Under normal circumstances, if input power is disconnected from the uninterruptible power supply, the SAN Volume Controller(s) connected to that uninterruptible power supply will perform a power down sequence. This operation, which saves the configuration and cache data to an internal disk in the SAN Volume Controller, typically takes about 3 minutes, at which time power is removed from the output of the uninterruptible power supply. In the event of a delay in the completion of the power down sequence, the uninterruptible power supply output power will be removed 5 minutes after the time that power was disconnected to the uninterruptible power supply. Since this operation is controlled by the SAN Volume Controller, an uninterruptible power supply that is not connected to an active SAN Volume Controller will not shut off within the 5 minute required period. In the case of an emergency, you will need to manually shut down the uninterruptible power supply by pushing the uninterruptible power supply power off button. |
| Attention: Data integrity could be compromised by pushing the uninterruptible power supply power off button. Never shut down an uninterruptible power supply without first shutting down the SAN Volume Controller nodes that it supports. |
It is very important that the two nodes in the I/O group are connected to a different uninterruptible power supply. This configuration ensures that the cache and cluster state information is protected against the failure of the uninterruptible power supply or of the mainline power source.
When nodes are added to the cluster, you must specify the I/O group they will join. The configuration interfaces will also check the uninterruptible power supply units and ensure that the two nodes in the I/O group are not connected to the same uninterruptible power supply units.
The following figure shows a cluster of four nodes, with two I/O groups and two uninterruptible power supply units.