This section describes the uninterruptible power supply.
Two external uninterruptible power supply units provide power to the SAN Volume Controller. Unlike the traditional uninterruptible power supply that enables continued operation of the devices that they supply when power is lost, these uninterruptible power supply units are used exclusively to maintain the data held in the SAN Volume Controller DRAM in the event of an unexpected loss of external power. The uninterruptible power supply units are required to power the SAN Volume Controllers even if the input power source is itself uninterruptible.
The uninterruptible power supply is connected to the SAN Volume Controllers with a power cable and a signal cable. To avoid the possibility of power and signal cables being connected to different uninterruptible power supply units these cables are wrapped together and supplied as a single field replaceable unit. The signal cables enable the SAN Volume Controllers to read status and identification information from the uninterruptible power supply.
Each SAN Volume Controller monitors the operational state of the uninterruptible power supply to which it is attached. If the uninterruptible power supply reports a loss of input power, the SAN Volume Controller stops all I/O operations and dumps the contents of its DRAM to the internal disk drive. When input power to the uninterruptible power supply is restored, the SAN Volume Controllers restart and restore the original contents of the DRAM from the data saved on the disk drive.
A SAN Volume Controller is not fully operational until the uninterruptible power supply charge state indicates that it has sufficient capacity to power the SAN Volume Controller for long enough to permit it to save all its memory to the disk drive in the event of a power loss. The uninterruptible power supply has sufficient capacity to save all the data on the SAN Volume Controller at least twice and so for a fully charged uninterruptible power supply even after battery capacity has been used to power the SAN Volume Controllers while they save DRAM data, sufficient battery capacity will remain to enable the SAN Volume Controllers to become fully operational as soon as input power is restored.
The following figure shows a picture of the uninterruptible power supply.

| Note: The SAN Volume Controller uninterruptible power supply is an integral part of the SAN Volume Controller solution and maintains continuous, SAN Volume Controller-specific communications with its attached SAN Volume Controller nodes. The SAN Volume Controller uninterruptible power supply must be used in accordance with documented guidelines and procedures and must not be used for any other purpose. |