Installing the uninterruptible power supply into
the rack
After you have completed the preparation
procedures for installing the uninterruptible power supply into the rack,
you are ready to install the uninterruptible power supply into the rack.
Prerequisites
Ensure that you have completed the following:
- The pre-installation procedures
- Installing the support rails for the uninterruptible power supply
- Preparing your uninterruptible power supply environment
 | Attention: Before you begin to install the uninterruptible power supply, read
through the safety and environmental notices. |
Steps
Perform the following steps to install the uninterruptible
power supply into the rack:
-
 | CAUTION: The uninterruptible power supply weighs 39 kg (86 lb) with the electronics
assembly and the battery assembly installed: |
- Do not attempt to lift the uninterruptible power supply
by yourself. Ask another service representative for assistance.
- Remove the battery assembly from the uninterruptible
power supply before removing the uninterruptible power supply from the shipping
carton.
- Do not attempt to install the uninterruptible power supply
into the rack unless the electronics assembly and the battery assembly have
been removed.
The weight of the uninterruptible power supply must be reduced by
removing the battery assembly before removing it from the shipping carton.
Perform the following steps to remove the battery assembly:
- Open the top of the uninterruptible power supply shipping carton; and
then, with the assistance of another service representative, grip the flaps
on either side of the uninterruptible power supply.
Figure 42. Opening the top of the uninterruptible power supply shipping carton
- Slide the uninterruptible power supply to the end of the carton and rest
its front edge of the edge of the carton as shown.
Figure 43. Sliding the uninterruptible power supply to the end of the carton
- Remove the two bolts 1 and additional nut 2 on
the left side of the bracket and remove the battery retaining bracket 3 .
Figure 44. Removing the battery retaining bracket
- Grip the tab on the front of the battery and pull the battery forward
until it can be accessed by two service representatives.
- With the assistance of another service representative lift the battery
assembly clear of the uninterruptible power supply and place to one side.
 | Note: The cover for the uninterruptible power supply is not installed,
however, it is included in the box with the uninterruptible power supply.
Install the front cover after you have completed the other installation steps. |
-
With the assistance of another service representative, lift
the uninterruptible power supply clear of the shipping carton and place it
on a flat, stable surface.
- Remove the two screws 1 , (see Figure 45).
 | CAUTION: The electronics assembly weighs 6.4 kg (14 lb). Take care when you remove
it from the uninterruptible power supply. |
Figure 45. Removing the uninterruptible power supply electronics assembly
- Pull the electronics assembly 2 out of the uninterruptible
power supply, and put it to one side.
- Stand at the front of the rack and, with aid from another service representative,
place the back of the uninterruptible power supply onto the support rails,
then slide the uninterruptible power supply into the rack.
- Install the front flathead screws 1 (see Figure 46).
Figure 46. Installing the uninterruptible power supply into a rack
- With aid from another service representative, reinstall the following
parts:
- Battery assembly
- Battery retaining bracket
- Electronics assembly
Attention: A grounding screw feature 2 is provided on the back of the uninterruptible power supply so that
you can attach a ground bonding wire if required by local wiring codes. Since
safety earthing of the uninterruptible power supply chassis is maintained
through the input line power cord, you are usually not required to use this
additional grounding screw feature.
- At the back of the uninterruptible power supply, plug the uninterruptible
power supply main power cable into the power socket 1 (see Figure 47).
Figure 47. Installing the uninterruptible power supply power cable
-
 | Attention: If possible, ensure that the two uninterruptible power supplies
are not both connected to the same power source. |
Plug the uninterruptible
power supply main cable into the main power source.
 | Attention: Ensure
that you comply with the following requirements for uninterruptible power
supplies:
|
 | Note: If the uninterruptible power supply
is cascaded from another uninterruptible power supply, the source uninterruptible
power supply must have at least 3 times the capacity per phase and the total
harmonic distortion must be less than 5% with any single harmonic being less
than 1%. The uninterruptible power supply also should have input voltage capture
that has a slew rate faster than 3 Hz per second and 1 msec glitch rejection. |
- All front panel indicators of the uninterruptible power supply flash for
a short time while the uninterruptible power supply runs a self test. When
the test is complete, the mode indicator 1 flashes to show
that the uninterruptible power supply is in standby mode (see Figure 48).
Press and hold the uninterruptible power supply on switch 2 until
you hear the uninterruptible power supply beep (approximately one second).
The mode indicator stops flashing and the load level indicators display the
percentage of load that is being supplied by the uninterruptible power supply.
The uninterruptible power supply is now in normal mode, and is charging its
battery.
Figure 48. Power switch and indicators of the uninterruptible power supply
If the mode indicator is flashing red and the alarm is sounding,
the voltage range alarm setting might not be correct. When a SAN Volume Controller is connected
to the uninterruptible power supply, the SAN Volume Controller automatically adjusts the voltage
range settings. Take no action for this alarm condition unless it persists
for more than five minutes after a SAN Volume Controller has been connected to this uninterruptible
power supply and powered on.
- Repeat this entire procedure to install the other uninterruptible power
supply.
 | Attention: The uninterruptible power supply is intended to maintain power
on SAN Volume Controller nodes until data can be saved to the local hard disk drive. Only SAN Volume Controller nodes
can be plugged into the uninterruptible power supply or the SAN Volume Controller cluster
will malfunction. |
Related topics