Installing the uninterruptible power supply into the rack Installing the uninterruptible power supply Connecting the uninterruptible power supply to the svc

After you have completed the preparation procedures for installing the uninterruptible power supply into the rack, you are ready to install the uninterruptible power supply into the rack.

Prerequisites

Ensure that you have completed the following:

Attention: Attention: Before you begin to install the uninterruptible power supply, read through the safety and environmental notices.
Steps

Perform the following steps to install the uninterruptible power supply into the rack:

  1. CAUTION:CAUTION: The uninterruptible power supply weighs 39 kg (86 lb) with the electronics assembly and the battery assembly installed:
    • Do not attempt to lift the uninterruptible power supply by yourself. Ask another service representative for assistance.
    • Remove the battery assembly from the uninterruptible power supply before removing the uninterruptible power supply from the shipping carton.
    • Do not attempt to install the uninterruptible power supply into the rack unless the electronics assembly and the battery assembly have been removed.

    The weight of the uninterruptible power supply must be reduced by removing the battery assembly before removing it from the shipping carton. Perform the following steps to remove the battery assembly:

    1. Open the top of the uninterruptible power supply shipping carton; and then, with the assistance of another service representative, grip the flaps on either side of the uninterruptible power supply.
      Figure 42. Opening the top of the uninterruptible power supply shipping carton
      Opening the top of the uninterruptible power supply shipping carton
    2. Slide the uninterruptible power supply to the end of the carton and rest its front edge of the edge of the carton as shown.
      Figure 43. Sliding the uninterruptible power supply to the end of the carton
      Sliding the uninterruptible power supply to the end of the carton
    3. Remove the two bolts  1  and additional nut  2  on the left side of the bracket and remove the battery retaining bracket  3 .
      Figure 44. Removing the battery retaining bracket
      Removing the battery retaining bracket
    4. Grip the tab on the front of the battery and pull the battery forward until it can be accessed by two service representatives.
    5. With the assistance of another service representative lift the battery assembly clear of the uninterruptible power supply and place to one side.
      Note:Note: The cover for the uninterruptible power supply is not installed, however, it is included in the box with the uninterruptible power supply. Install the front cover after you have completed the other installation steps.
  2. With the assistance of another service representative, lift the uninterruptible power supply clear of the shipping carton and place it on a flat, stable surface.
  3. Remove the two screws  1  , (see Figure 45).
    CAUTION:CAUTION: The electronics assembly weighs 6.4 kg (14 lb). Take care when you remove it from the uninterruptible power supply.
    Figure 45. Removing the uninterruptible power supply electronics assembly
    Removing the uninterruptible power supply electronics assembly
  4. Pull the electronics assembly  2  out of the uninterruptible power supply, and put it to one side.
  5. Stand at the front of the rack and, with aid from another service representative, place the back of the uninterruptible power supply onto the support rails, then slide the uninterruptible power supply into the rack.
  6. Install the front flathead screws  1  (see Figure 46).
    Figure 46. Installing the uninterruptible power supply into a rack
    Installing the uninterruptible power supply into a rack
  7. With aid from another service representative, reinstall the following parts:
    1. Battery assembly
    2. Battery retaining bracket
    3. Electronics assembly
    Attention: A grounding screw feature  2  is provided on the back of the uninterruptible power supply so that you can attach a ground bonding wire if required by local wiring codes. Since safety earthing of the uninterruptible power supply chassis is maintained through the input line power cord, you are usually not required to use this additional grounding screw feature.
  8. At the back of the uninterruptible power supply, plug the uninterruptible power supply main power cable into the power socket  1  (see Figure 47).
    Figure 47. Installing the uninterruptible power supply power cable
    Installing the uninterruptible power supply power cable
  9. Attention: Attention: If possible, ensure that the two uninterruptible power supplies are not both connected to the same power source.
    Plug the uninterruptible power supply main cable into the main power source.
    Attention: Attention: Ensure that you comply with the following requirements for uninterruptible power supplies:
    Note:Note: If the uninterruptible power supply is cascaded from another uninterruptible power supply, the source uninterruptible power supply must have at least 3 times the capacity per phase and the total harmonic distortion must be less than 5% with any single harmonic being less than 1%. The uninterruptible power supply also should have input voltage capture that has a slew rate faster than 3 Hz per second and 1 msec glitch rejection.
  10. All front panel indicators of the uninterruptible power supply flash for a short time while the uninterruptible power supply runs a self test. When the test is complete, the mode indicator  1  flashes to show that the uninterruptible power supply is in standby mode (see Figure 48).

    Press and hold the uninterruptible power supply on switch  2  until you hear the uninterruptible power supply beep (approximately one second). The mode indicator stops flashing and the load level indicators display the percentage of load that is being supplied by the uninterruptible power supply. The uninterruptible power supply is now in normal mode, and is charging its battery.

    Figure 48. Power switch and indicators of the uninterruptible power supply
    Power switch and indicators of the uninterruptible power supply

    If the mode indicator is flashing red and the alarm is sounding, the voltage range alarm setting might not be correct. When a SAN Volume Controller is connected to the uninterruptible power supply, the SAN Volume Controller automatically adjusts the voltage range settings. Take no action for this alarm condition unless it persists for more than five minutes after a SAN Volume Controller has been connected to this uninterruptible power supply and powered on.

  11. Repeat this entire procedure to install the other uninterruptible power supply.
Attention: Attention: The uninterruptible power supply is intended to maintain power on SAN Volume Controller nodes until data can be saved to the local hard disk drive. Only SAN Volume Controller nodes can be plugged into the uninterruptible power supply or the SAN Volume Controller cluster will malfunction.
Related topics Installing the uninterruptible power supply Connecting the uninterruptible power supply to the svc