Installing the support rails for the uninterruptible power supply Installing the uninterruptible power supply Installing the uninterruptible power supply into the rack

This task describes how to install the support rails for the uninterruptible power supply.

Steps

Perform the following steps to install the support rails for the uninterruptible power supply:

  1. Refer to the customer's hardware location table to find out where in the rack the uninterruptible power supplies are to be installed.
    Note:Note: If you are installing the SAN Volume Controller into a rack that already contains other SAN Volume Controllers and uninterruptible power supplies, the installed uninterruptible power supplies might have spare capacity. If the customer intends to use that spare capacity, the SAN Volume Controllers that you are going to install might have been delivered without uninterruptible power supplies.
  2. Discard the two handles and their associated nuts that are shipped with the support rails for the uninterruptible power supply.
  3. At the back of the rack, observe the EIA positions, and determine where you are going to install the uninterruptible power supply (see Figure 41). A uninterruptible power supply must always be installed into the lowest available position in the rack. The only device that can be below a uninterruptible power supply is another uninterruptible power supply.
    Note:Note: The bottom of the flange of the support rail must align with the EIA mark on the rack.
    Figure 41. Installing support rails for a uninterruptible power supply into the rack
    Installing support rails for a uninterruptible power supply into the rack
  4. Perform the following steps for each rail:
    1. Attach nut clips  4  to the rack. These nut clips must align with the second and fourth holes of the support rail flange.
    2. Loosen the two wing nuts  2 .
    3. Loosen the wing nut  3  and slide the bracket toward the back of the rail.
    4. Remain at the back of the rack, hold the support rail in position in the rack, then install and fully tighten the two mounting screws  5 .
    5. Go to the front of the rack.
    6. Extend the support rail toward the front of the rack.
      Note:Note: Hold the support rail in position until you have completed step 4h.
    7. Ensure that the support rail is horizontal (a level might be useful here).
    8. Install the two mounting screws  1  into the third and fourth holes of the support rail flange. Fully tighten the screws.
    9. Fully tighten the two wing nuts  2 .
    10. Loosen the wing nut  3  and slide the bracket toward the front of the rail, as far as it will go, with the front edge of the bracket against the back end of the front support rail. Fully tighten the wing nut  3 .
Related topics Installing the uninterruptible power supply Installing the uninterruptible power supply into the rack