MAP 5500: Ethernet Using the MAPs MAP 5600: Fibre-channel

This map helps you to solve problems that have occurred on the SAN Volume Controller Ethernet.

Prerequisites

If you are not familiar with these MAPs, read using the maps first.

Context

You might have been sent here for one of the following reasons:

Steps

Perform the following steps:

  1. Display the Ethernet status, using the Front panel display.

    Does the display read failed?

    NO
    Go to step 2.
    YES
    Go to step 5.
  2. Display Node Error if present, using the Front panel display.

    Is the front panel displaying Node Error with error code 540?

    NO
    Go to step 3.
    YES
    Go to step 5.
  3. (from step 2)

    Display Cluster Error if present, using the Front panel display.

    Is the front panel displaying Cluster Error with error code 1400?

    NO
    Go to step 4.
    YES
    Go to step 5.
  4. (from step 3)

    Display the Ethernet port status, using the Front panel display.

    Is the display showing an Ethernet port status status of Failed?

    NO
    Go to step 8.
    YES
    Go to step 5.
  5. (from steps 1, 2, 3, and 4)

    Is the green LED on the upper left of the Ethernet port assembly illuminated?

    NO
    The Ethernet connection between the SAN Volume Controller and the Ethernet network is faulty. If a spare Ethernet cable is available, connect the replacement cable between the lower and upper Ethernet connectors on the back of the SAN Volume Controller. If a spare Ethernet cable is not available select a node with an Ethernet port status of Inactive (this is working but not currently being used). Remove this cable and connect it between the upper and lower Ethernet connectors as described above.
    Note:Note: Remove and retain any blanking plate over the unused upper Ethernet connector. Go to step 6.
    YES
    Go to step 7.
  6. (from step 5)

    Are the green LEDs on the upper left and upper right of the Ethernet port assembly both illuminated?

    NO
    Ethernet interfaces on the system board assembly are not working correctly.
    • Perform the following tasks:
      • Replace the system board assembly.
      • Verify the repair by continuing with the repair verification MAP.
    YES
    The Ethernet connection between the SAN Volume Controller and the Ethernet network is faulty.

    Perform the following tasks:

    • Remove the test cable inserted in step 5.
    • Replace any blanking plate retained in step 5 to the upper Ethernet connector.
    • Replace the Ethernet cable with a new cable and display the Ethernet port status. If the status is still Failed:
      1. Use the problem determination procedures for your Ethernet hub to resolve an Ethernet network connection problem.
      2. Verify the repair by continuing with the repair verification MAP.
  7. (from step 5)

    Display the Ethernet status, using the Front panel display.

    Is the displayed status failed?

    NO
    Go to step 8.
    YES
    Ethernet connected LED shows an active Ethernet connection to the SAN Volume Controller. However, service display shows Ethernet Failed
    1. Replace the system board assembly.
    2. Verify the repair by continuing with the repair verification MAP.
  8. (from step 7.

    A previously reported fault with the Ethernet interface is no longer being shown.

    Check with the customer that the Ethernet interface has not been intentionally disconnected, and that there is no recent history of fixed Ethernet problems with other components of the Ethernet network.

    Is the Ethernet failure explained by the above checks?

    NO
    Perform steps in the following sequence:
    1. Replace the Ethernet cable
    2. Use Ethernet hub problem determination procedure to resolve an Ethernet network connection problem.
    3. Replace the system board assembly.
    4. Verify the repair by continuing with the repair verification MAP.
    YES
    Verify the repair by continuing with the repair verification MAP.
Related topics Using the MAPs MAP 5600: Fibre-channel