Connecting the uninterruptible power supply to the SAN Volume Controller Installing the uninterruptible power supply

To provide redundancy and concurrent maintenance, the SAN Volume Controllers must be installed in pairs.

Each SAN Volume Controller of a pair must be connected to a different uninterruptible power supply. Each uninterruptible power supply can support four SAN Volume Controllers.

Note:Note: You must have two uninterruptible power supplies per cluster. A cluster can contain no more than four SAN Volume Controllers. Also, each uninterruptible power supply of a pair must be connected to a separate electrical input power source (if possible) to reduce the chance of input power failure at both uninterruptible power supplies.

The uninterruptible power supply requires a dedicated branch circuit that meets the following specifications:

  • A 15A circuit breaker must be installed in each branch circuit that supplies the power to a uninterruptible power supply.
  • Single-phase.
  • 200 - 240 V.

The SAN Volume Controller software determines whether the input voltage to the uninterruptible power supply is within range and sets an appropriate voltage alarm range on the uninterruptible power supply. The software continues to re-check the input voltage every few minutes; if it changes substantially but remains within the permitted range, the alarm limits are readjusted.