To provide redundancy and concurrent maintenance, the SAN Volume Controllers must be installed in pairs.
Each SAN Volume Controller of a pair must be connected to a different uninterruptible power supply. Each uninterruptible power supply can support four SAN Volume Controllers.
| Note: You must have two uninterruptible power supplies
per cluster. A cluster can contain no more than four SAN Volume Controllers. Also, each uninterruptible
power supply of a pair must be connected to a separate electrical input power
source (if possible) to reduce the chance of input power failure at both uninterruptible
power supplies.
The uninterruptible power supply requires a dedicated branch circuit that meets the following specifications:
|
The SAN Volume Controller software determines whether the input voltage to the uninterruptible power supply is within range and sets an appropriate voltage alarm range on the uninterruptible power supply. The software continues to re-check the input voltage every few minutes; if it changes substantially but remains within the permitted range, the alarm limits are readjusted.