Connecting the SAN Volume Controller to the uninterruptible power supply Installing Connecting the svc to the SAN and to the Ethernet network

This task includes the steps you complete to connect the SAN Volume Controller to the uninterruptible power supply.

Each SAN Volume Controller of a pair should be connected to a different uninterruptible power supply. Each uninterruptible power supply can support up to two SAN Volume Controllers.

Attention: Attention: Do not connect two clusters to the same pair of uninterruptible power supplies. Both clusters will be lost in the event that a power failure occurs on both of those uninterruptible power supplies.
Note:Note: You must have two uninterruptible power supplies per cluster. A cluster can contain no more than four SAN Volume Controllers. Also, each uninterruptible power supply of a pair must be connected to a separate electrical input power source (if possible) to reduce the chance of input power failure at both uninterruptible power supplies.

The SAN Volume Controller software determines whether the input voltage to the uninterruptible power supply is within range and sets an appropriate voltage alarm range on the uninterruptible power supply. The software continues to re-check the input voltage every few minutes; if it changes substantially but remains within the permitted range, the alarm limits are readjusted.

Prerequisites

Before you begin this task, refer to the customer's cable connection table in the IBM TotalStorage SAN Volume Controller: Planning Guide to identify the uninterruptible power supply to which this SAN Volume Controller is to be connected.

Steps

Perform the following steps to connect the SAN Volume Controller to the uninterruptible power supply.

  1. At the back of the SAN Volume Controller, plug a power cable into the socket  1  (see Figure 55).
    Figure 55. Connecting the SAN Volume Controller power cable to the uninterruptible power supply
    Connecting the SAN Volume Controller power cable to the uninterruptible power supply
  2. Plug the serial cable of the power cable assembly into the serial socket  2 .
  3. DANGERDANGER You have already switched on the uninterruptible power supply. The output sockets of the uninterruptible power supply are live.
    Plug the free end of the SAN Volume Controller power cable into any vacant output socket  3  on the uninterruptible power supply.
  4. Plug the free end of the signal cable into any vacant position on the top row of serial connectors  4  on the uninterruptible power supply. Do not plug any serial cables into the bottom row of serial connectors or the uninterruptible power supply will malfunction.
Result

The SAN Volume Controller power is connected to the uninterruptible power supply.

Related topics Installing Connecting the svc to the SAN and to the Ethernet network