Cable connection table Preparing the physical configuration Completing the configuration data table

Complete the cable connection table to indicate how you want to connect the units in the rack.

Table 12. Cable connection table
SAN Volume Controller Uninterruptible power supply Ethernet hub or switch FC port-1 FC port-2 FC port-3 FC port-4
    
    
    
    
    
    

Master console Ethernet FC port-1 FC port-2
Public network VPN
                            

Example of a completed cable connection table:

For this example, assume you are completing the cabling details for the system. Remember that SAN Volume Controllers are configured in pairs, and that the two SAN Volume Controllers of a pair must not be connected to the same uninterruptible power supply. Also, the two uninterruptible power supply units of a pair should not be connected to the same power source to reduce the chance of input power failure at both uninterruptible power supply units. For this example, assume that the pairs of SAN Volume Controllers are: node 1 and node 2, and node 3 and node 4, and that the two power sources provided by the uninterruptible power supply units are A and B.

Note:Note: The uninterruptible power supply requires two dedicated branch circuits that meet the following specifications:
  • 15 amp circuit breaker in each branch circuit that supplies the power to an uninterruptible power supply
  • Single-phase
  • 50 - 60 Hz
  • 220 volt

For the Ethernet connection, you must use Ethernet port 1 of the SAN Volume Controller. Do not use any other Ethernet port, because the software is configured for Ethernet port 1 only.

Note:Note: All SAN Volume Controller nodes that are part of the same cluster must be connected to the same Ethernet subnet, otherwise TCP/IP address failover will not work.

The following table is an example of what the completed table might look like for this example.

Table 13. Example of cable connection table
SAN Volume Controller Uninterruptible power supply Ethernet hub or switch FC Port-1 FC Port-2 FC Port-3 FC Port-4
Node 1
Uninterruptible power supply A

Hub
or switch 1,
Port 1
FC switch 1, Port 1 FC switch 2, Port 1 FC switch 1, Port 2 FC switch 2, Port 2
Node 2 Uninterruptible power supply A
Hub
or switch 1,
Port 2
FC switch 1, Port 3 FC switch 2, Port 3 FC switch 1, Port 4 FC switch 2, Port 4
Node 3 Uninterruptible power supply B
Hub
or switch 1,
Port 3
FC switch 1, Port 5 FC switch 2, Port 5 FC switch 1, Port 6 FC switch 2, Port 6
Node 4
Uninterruptible power supply B

Hub
or switch 1,
Port 4
FC switch 1, Port 7 FC switch 2, Port 7 FC switch 1, Port 8 FC switch 2, Port 8
Master console Ethernet FC switch 1, Port-9 FC switch 2, Port-9
Public network VPN
Master console Ethernet hub 1, Port 5 Ethernet hub 1, Port 6 FC Port-1 FC switch 1, Port 9 FC Port-2 FC switch 2, Port 9
Related topics Preparing the physical configuration Completing the configuration data table