Complete the cable connection table to indicate how you want to connect the units in the rack.
| SAN Volume Controller | Uninterruptible power supply | Ethernet hub or switch | FC port-1 | FC port-2 | FC port-3 | FC port-4 |
|---|---|---|---|---|---|---|
| Master console | Ethernet | FC port-1 | FC port-2 | |
|---|---|---|---|---|
| Public network | VPN | |||
Example of a completed cable connection table:
For this example, assume you are completing the cabling details for the system. Remember that SAN Volume Controllers are configured in pairs, and that the two SAN Volume Controllers of a pair must not be connected to the same uninterruptible power supply. Also, the two uninterruptible power supply units of a pair should not be connected to the same power source to reduce the chance of input power failure at both uninterruptible power supply units. For this example, assume that the pairs of SAN Volume Controllers are: node 1 and node 2, and node 3 and node 4, and that the two power sources provided by the uninterruptible power supply units are A and B.
Note: The uninterruptible
power supply requires
two dedicated branch circuits that meet the following specifications:
|
For the Ethernet connection, you must use Ethernet port 1 of the SAN Volume Controller. Do not use any other Ethernet port, because the software is configured for Ethernet port 1 only.
| Note: All SAN Volume Controller nodes that are part of the same cluster must be connected to the same Ethernet subnet, otherwise TCP/IP address failover will not work. |
The following table is an example of what the completed table might look like for this example.
| SAN Volume Controller | Uninterruptible power supply | Ethernet hub or switch | FC Port-1 | FC Port-2 | FC Port-3 | FC Port-4 |
|---|---|---|---|---|---|---|
| Node 1 | Uninterruptible power supply A |
Hub or switch 1, Port 1 |
FC switch 1, Port 1 | FC switch 2, Port 1 | FC switch 1, Port 2 | FC switch 2, Port 2 |
| Node 2 | Uninterruptible power supply A | Hub or switch 1, Port 2 |
FC switch 1, Port 3 | FC switch 2, Port 3 | FC switch 1, Port 4 | FC switch 2, Port 4 |
| Node 3 | Uninterruptible power supply B | Hub or switch 1, Port 3 |
FC switch 1, Port 5 | FC switch 2, Port 5 | FC switch 1, Port 6 | FC switch 2, Port 6 |
| Node 4 | Uninterruptible power supply B |
Hub or switch 1, Port 4 |
FC switch 1, Port 7 | FC switch 2, Port 7 | FC switch 1, Port 8 | FC switch 2, Port 8 |
| Master console | Ethernet | FC switch 1, Port-9 | FC switch 2, Port-9 | |
|---|---|---|---|---|
| Public network | VPN | |||
| Master console | Ethernet hub 1, Port 5 | Ethernet hub 1, Port 6 | FC Port-1 FC switch 1, Port 9 | FC Port-2 FC switch 2, Port 9 |