1165
 
Explanation:

The uninterruptible power supply output load is unexpectedly high. The uninterruptible power supply output is possibly connected to an extra non-SAN Volume Controller load.

Action:

  1. Ensure that only SAN Volume Controllers are receiving power from the uninterruptible power supply. Ensure that there are no switches or disk controllers that are connected to the uninterruptible power supply.
  2. Check node status (refer to "Viewing the node status using the SAN Volume Controller Console application on the master console" for the user interface or "Checking the status of the node" for the command line interface). If all nodes show a status of "online," mark the error you have just repaired "fixed." If any nodes do not show a status of "online," go to start map. If you return to this step, contact the IBM support center to resolve the problem with the uninterruptible power supply.
  3. Go to repair verification map.

Possible Cause-FRUs or other:

Other:
Related topics:

(C) Copyright International Business Machines Corporation 2003, 2004