1160
 
Explanation:

A problem with too much load current has occurred in the uninterruptible power supply (reported by uninterruptible power supply alarm bits).

Action:

  1. Ensure that only SAN Volume Controllers are receiving power from the uninterruptible power supply. Ensure that there are no switches or disk controllers that are connected to the uninterruptible power supply.
  2. Disconnect the SAN Volume Controllers one at a time from the uninterruptible power supply until the problem with too much load current is removed; that is, you have disconnected the SAN Volume Controller that is causing too much load current. On that SAN Volume Controller, exchange in the sequence shown, the FRUs for new FRUs. See "Possible Cause-FRUs or other" after the last action in this section.
  3. Check node status (refer to "Viewing the node status using the SAN Volume Controller Console application on the master console" for the user interface or "Checking the status of the node" for the command line interface). If all nodes show a status of "online," mark the error you have just repaired "fixed." If any nodes do not show a status of "online," go to start map. If you return to this step, contact the IBM support center to resolve the problem with the uninterruptible power supply.
  4. Go to repair verification map.

Possible Cause-FRUs or other: