Explanation:

The signal connection between a SAN Volume Controller and its uninterruptible power supply is failing.

Action:

  1. If other SAN Volume Controllers that are using this uninterruptible power supply are reporting this error, exchange the uninterruptible power supply electronics unit for a new one.
  2. If only this SAN Volume Controller is reporting the problem, check that the signal cable, which is part of the power cable assembly, is secure at both ends. If signal cable is secure, exchange the FRUs for new FRUs in the sequence shown. See "Possible Cause-FRUs or other" after the last action in this section.
  3. Check node status (refer to "Viewing the node status using the SAN Volume Controller Console application on the master console" for the user interface or "Checking the status of the node" for the command line interface). If all nodes show a status of "online," mark the error you have just repaired "fixed." If any nodes do not show a status of "online," go to start map. If you return to this step, contact the IBM support center to resolve the problem with the uninterruptible power supply.
  4. Go to repair verification map.