The uninterruptible power supply has reported an ambient over temperature.
The uninterruptible power supply switches to Bypass mode to allow the uninterruptible
power supply to cool.
Action:
Power off the nodes attached to the uninterruptible power supply.
Turn off the uninterruptible power supply, and then unplug the uninterruptible
power supply from the main power source.
Ensure that the air vents of the uninterruptible power supply are not
obstructed.
Ensure that the air flow round the uninterruptible power supply is not
restricted.
Wait for at least five minutes, then restart the uninterruptible power
supply. If the problem remains, check the ambient temperature. Correct if
necessary. Otherwise, exchange the FRU for a new FRU. See "Possible Cause-FRUs
or other" after the last action in this section.
Check node status (refer to "Viewing the node status using
the SAN Volume Controller Console application on the master console" for the user interface or "Checking
the status of the node" for the command line interface). If all nodes
show a status of "online," mark the error you have just repaired "fixed."
If any nodes do not show a status of "online," go to start map. If
you return to this step, contact the IBM support center to resolve the problem
with the uninterruptible power supply.
Go to repair verification map.
Possible Cause-FRUs or other:
Uninterruptible power supply electronics unit (50%)
Other:
The system ambient temperature is outside the specification
(50%)