1135
 
Explanation:

The uninterruptible power supply has reported an ambient over temperature. The uninterruptible power supply switches to Bypass mode to allow the uninterruptible power supply to cool.

Action:

  1. Power off the nodes attached to the uninterruptible power supply.
  2. Turn off the uninterruptible power supply, and then unplug the uninterruptible power supply from the main power source.
  3. Ensure that the air vents of the uninterruptible power supply are not obstructed.
  4. Ensure that the air flow round the uninterruptible power supply is not restricted.
  5. Wait for at least five minutes, then restart the uninterruptible power supply. If the problem remains, check the ambient temperature. Correct if necessary. Otherwise, exchange the FRU for a new FRU. See "Possible Cause-FRUs or other" after the last action in this section.
  6. Check node status (refer to "Viewing the node status using the SAN Volume Controller Console application on the master console" for the user interface or "Checking the status of the node" for the command line interface). If all nodes show a status of "online," mark the error you have just repaired "fixed." If any nodes do not show a status of "online," go to start map. If you return to this step, contact the IBM support center to resolve the problem with the uninterruptible power supply.
  7. Go to repair verification map.

Possible Cause-FRUs or other:

Other:
Related topics: